A thermal-hydraulic comparison of liquid microchannel and impinging liquid jet array heat sinks for high power electronics cooling
Citation:
A. J. Robinson 'A Thermal-hydraulic comparison of liquid microchannel and impinging liquid jet array heat sinks for high power electronics cooling' in IEEE Transactions on Components and Packaging Technologies, 32, (2), 2009, pp 347 - 357Download Item:
Abstract:
In this paper, two single-phase liquid cooling strategies
for electronics thermal management are compared and contrasted;
impinging jet arrays and laminar flow in microchannels.
The comparison is posed for a situation in which an electronic device
must dissipate 250 W/cm? while being maintained at a temperature
of 85 C. The calculations indicate that both the impinging
jet and microchannel heat sinks can provide the necessary cooling
with less than 0.1Wof pumping power. Microchannels achieve this
heat transfer target with such low pumping power by the relatively
high pressure drop being offset by a low volumetric flow rate. In
contrast, impinging jet heat sinks require a lower pressure drop
and higher volumetric flow rate. From a practical point of view,
lower operating pressure and larger mass flow rates are desirable
characteristics, since they will be less prone to leakage and will provide
better temperature uniformity across the heated component.n
Sponsor
Grant Number
Science Foundation Ireland
Author's Homepage:
http://people.tcd.ie/arobinsDescription:
PUBLISHED
Author: ROBINSON, ANTHONY
Publisher:
IEEEType of material:
Journal ArticleSeries/Report no:
IEEE Transactions on Components and Packaging Technologies32
2
Availability:
Full text availableMetadata
Show full item recordLicences: